CHAPTER 3
Small Configuration
Installing the 23-Inch (FC9682HSW2) Heat Baffle
FNC-7500-0061-200
Issue 1, May 2009
FLASHWAVE 7500 Release 6.1
Equipment Installation
3-46
Fujitsu and Fujitsu Customer Use Only
This procedure provides instructions for installing the 23-inch (FC9682HSW2) heat baffle
(see Figure 3-29 [p. 3-45]) in a 23-inch relay rack.
Note: The 19-inch (FC9503HSW3) heat baffle can also be installed in a 23-inch rack for use for
Small Configuration systems. Refer to Section 3.10, Installing the 19-Inch (FC9682HSW3) Heat
Baffle [p. 3-47].
1 If not already done, remove the heat baffle from the shipping container.
2 Secure the heat baffle to the rack using two rack mounting screws on each side of the
assembly.
Note: Ensure that the heat baffle is oriented as shown in Figure 3-29 [p. 3-45] so that air pushed
upward from below is deflected to the rear. If the heat baffle is mounted under the shelf, use the same
orientation so that air enters the shelf from the front of the rack.
This procedure is complete.