CHAPTER 3
Small Configuration
Installing the 23-Inch (FC9682HSW2) Heat Baffle
3-45
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
3.9 Installing the 23-Inch (FC9682HSW2) Heat Baffle
When used, the heat baffle is positioned directly above or beneath an Optical or Tributary
shelf (see Figures 3-1 [p. 3-5] through 3-11 [p. 3-15]). If it is positioned above the shelf, as
shown in Figure 3-29 [p. 3-45], the heat baffle ensures that air pushed upward through the
shelf is deflected to the rear of the rack. If it is positioned under the shelf, the heat baffle
ensures that air entering from below comes from the front of the rack.
Figure 3-29: Typical Shelf Mounting with Heat Baffle
(Small Configuration)
7"
4"
3"
4"
Heat Baffle
m1656mi_3