EasyManua.ls Logo

Fujitsu FLASHWAVE 7500 - Checking Ground Resistance at the Optical;Tributary Shelf Power Input

Fujitsu FLASHWAVE 7500
392 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4
ETSI Configuration
Checking Ground Resistance at the Optical/Tributary Shelf Power Input
4-75
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
4.15 Checking Ground Resistance at the Optical/Tributary
Shelf Power Input
Ideally, frame ground and battery return at the shelf power input connectors are common to
each other. Essentially a resistance of 0 ohms should be present between them and little or no
voltage potential across frame ground and battery return.
The test equipment required is a DMM or a voltmeter and ohmmeter that can accurately
detect low resistance levels. See Figure 4-50 [p. 4-75].
Step Task
1 Use the DMM set to the voltmeter function or a voltmeter to measure the voltage between
frame ground and each of the battery return points. The reading should be very close to 0 V
DC.
2 Does the voltage exceed 1 V DC?
If YES:
Do not continue with Step 3 [p. 4-76] until the voltage source has been eliminated. For
technical assistance, call 1-800-USE-FTAC (800-873-3822).
If NO:
Continue with Step 3 [p. 4-76].
Figure 4-50: Ground Voltage Check Example
DMM
-48
VOLTS
DC
+
–AMP
MAIN A G A
FG
m1718pp_1
Revision 1, June 2009

Table of Contents

Related product manuals