CHAPTER 4
ETSI Configuration
Installing the ETSI (FC9682HSW4) Heat Baffle
4-29
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
4.9 Installing the ETSI (FC9682HSW4) Heat Baffle
The ETSI heat baffle is positioned directly above an ETSI core shelf and directly under a
DCM or LAM/DCM shelf (see Figure 4-13 [p. 4-29]). The heat baffle ensures that air
pushed upward through the shelf below is deflected to the front of the rack.
This procedure provides instructions for installing the ETSI (FC9682HSW4) heat baffle (see
Figure 4-13 [p. 4-29]) in an ETSI rack.
Step Task
1 If not already done, remove the heat baffle from the shipping container.
2 Secure the heat baffle to the rack using two rack mounting screws on each side of the
assembly.
Note: Ensure that the heat baffle is oriented as shown in Figure 4-13 [p. 4-29] so that air pushed
upward from below is deflected to the rear. If the heat baffle is mounted under the shelf, use the same
orientation so that air enters the shelf from the front of the rack.
This procedure is complete.
Figure 4-13: HSW4 Heat Baffle
(ETSI Configuration)
Side View
Front View
Top View
m1718nf_1