Installing Power, Ground, and Alarm Cables
FNC-7500-0061-200
Issue 1, May 2009
FLASHWAVE 7500 Release 6.1
Equipment Installation
5-24
Fujitsu and Fujitsu Customer Use Only
5.10 Installing Power, Ground, and Alarm Cables
This procedure provides instructions for installing power, ground, and alarm cabling for
standard rack configurations.
It includes the following subprocedures: Procedure
5.10.1 Reference Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5.10.2 Install Power, Ground, and Alarm Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-35
5.10.1 Reference Material
The cables and cable harnesses are listed in Table 5-1 [p. 5-24] and shown in Figure 5-10
[p. 5-25].
Note: Connections to the shelf power terminal strip should use copper conductors only.
Table 5-1: Power, Ground, and Alarm Cable Connections
(Extension Configuration)
Part Number Use Description Term Type Wire Gauge
HA15B-0001-C413 –48 V DC and
ground
5-wire rack/shelf power harness,
one set per shelf
10 AWG crimp
lugs
10 AWG
HA660-1106-T003 Rack alarms 6-connector daisy-chained alarm
harness, one connector per shelf
(CNA through CNF), one harness
per rack
D-sub 25-pin,
terminates with
wire-wrap at CBP
24 AWG
HA660-1102-T015 Shelf alarms Alarm cable from rack alarm cable
connector to shelf backplane alarm
connector, one per shelf
D-sub 25-pin,
CN1 at rack
alarm end, CN2
at shelf alarm end
24 AWG
PC15L-0001-C045 Frame ground Frame ground stranded wire cable
from rack to CBP, one per rack
Terminal lugs,
both ends,
installed
6 AWG, stranded