CHAPTER 3
Small Configuration
Installing the LAS2 Shelf
FNC-7500-0061-200
Issue 1, May 2009
FLASHWAVE 7500 Release 6.1
Equipment Installation
3-68
Fujitsu and Fujitsu Customer Use Only
11 Using four pan-head Phillips M4 screws (8 mm long) on each side, secure the left and right
shelf flanges to the FC9503LAS2 shelf as shown in Figure 3-51 [p. 3-64].
Figure 3-56 [p. 3-68] shows a right-side view of the FC9503LAS2 shelf after the flange is
mounted.
12 Secure the FC9503LAS2 shelf to the rack using three rack mounting screws on each side of
the assembly.
Note: If hole alignment does not permit three screws on each side, securing the shelf with only two
screws on each side is acceptable.
This procedure is complete.
3.13.2 Install FC9682LAS2 Shelf
The FC9682LAS2 shelf has a nominal width of 19 inches and can be installed in either a
19-inch relay rack (see Figure 3-57 [p. 3-69]) or a 23-inch relay rack (see Figure 3-58
[p. 3-70]). In either case, two flanges are used. Table 3-7 [p. 3-70] lists the flange kit part
numbers for the FC9682LAS2 shelf.
Do not attempt to handle and install the shelves without sufficient assistance. The LAS2
shelf weighs approximately 15 lb (7 kg) empty (without LAMs). Equipped, the LAS2 weighs
significantly more. Handling the equipment without sufficient assistance may result in
personal injury, damage to the equipment, or both.
Do not use the internal walls of any shelf as a lifting point or lift support. Doing so may
damage the plug-in unit rail support.
Figure 3-56: Flange Mounted on Right Side of FC9503LAS2 Shelf (23-Inch Rack Installation)