Equipment Installation
1 INTRODUCTION
This practice contains general installation procedures for the FLASHWAVE® 7500 system.
Installation teams should use these procedures for installing equipment racks and shelves,
circuit breaker panels, wiring and cabling, and other miscellaneous items. Shelf backplane
connectors and rack/shelf grounding information is also provided.
For a detailed description of the FLASHWAVE 7500 plug-in unit installation procedures,
initial application of power to the system and system provisioning, refer to System Turn-Up, or
to System Turn-Up.
FLASHWAVE 7500 system is a Class I laser product incorporating Class I and IIIb laser
diodes. It complies with FDA Radiation Performance Standards, 21CFR1040.10.
FLASHWAVE 7500 system should be installed only in restricted access areas in accordance
with articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFA 70.
FLASHWAVE 7500 equipment should be rack mounted above a concrete, or other
noncombustible, surface only.
The power source for FLASHWAVE 7500 equipment should be reliably earth-grounded.
The FLASHWAVE 7500 system is intended to be grounded to an Isolated Bonding Network
(IBN). However, the system can be deployed in a Common Bonding Network (CBN) if
properly configured.
Revision 1, June 2009