CHAPTER 5
Extension Configuration
Installing Power, Ground, and Alarm Cables
FNC-7500-0061-200
Issue 1, May 2009
FLASHWAVE 7500 Release 6.1
Equipment Installation
5-26
Fujitsu and Fujitsu Customer Use Only
Figures 5-11 [p. 5-27] through 5-13 [p. 5-29] show schematics for installing power, ground,
and alarm cabling between the rack, shelves and CBP for the following standard rack
configurations:
■
Rack with one Universal shelf (Figure 5-11 [p. 5-27])
■
Rack with two Universal shelves (Figure 5-12 [p. 5-28])
■
Rack with three Universal shelves (Figure 5-13 [p. 5-29])
Each standard rack configuration includes a circuit breaker panel (CBP) with power terminals
as shown in Figure 5-14 [p. 5-30]. The circuit breakers within the CBP are associated with
shelves listed in Table 5-2 [p. 5-30].
Figure 5-15 [p. 5-31] shows the Extension shelf backplane. Figure 5-16 [p. 5-32] shows the
power cabling.
Figure 5-17 [p. 5-33] shows the rack alarm cable harness, which gets wire wrapped to the
CBP. Connectors along this harness mate to shelf alarm cables (see Figure 5-18 [p. 5-34]) that
plug into alarm ports on the shelf backplane.