CHAPTER 5
Extension Configuration
Installing Power, Ground, and Alarm Cables
FNC-7500-0061-200
Issue 1, May 2009
FLASHWAVE 7500 Release 6.1
Equipment Installation
5-40
Fujitsu and Fujitsu Customer Use Only
27 Prepare the power leads by installing the terminal lugs (wrapped in a plastic bag shipped with
the cable) that are required on one end of the cable (see Figure 5-10 [p. 5-25]). Ensure that no
wire strands are shorting terminals together and that leads are securely fastened. The cable
should now have terminal lugs on both ends of the power cable.
Note: The shelf power wiring is the same with all rack configurations. Observe the color coding of the
power cable.
28 On the backplane of the shelf identified in Step 25 [p. 5-39], remove the plastic cover on the
shelf power terminal strip located on the bottom right of the shelf backplane (see Figure 5-16
[p. 5-32]).
29 Connect both ends of cable GA of the power harness as follows:
a. Identify lug GA in the power harness (see Figure 5-10 [p. 5-25]) and connect it to shelf
terminal GA (see Figure 5-16 [p. 5-32]).
b. Connect the other end of the same cable to CBP terminal RTN A1 CB3 (see
Figure 5-14 [p. 5-30]).
30 Connect both ends of cable GB of the power harness as follows:
a. Identify lug GB in the power harness (see Figure 5-10 [p. 5-25]) and connect it to shelf
terminal GB (see Figure 5-16 [p. 5-32]).
b. Connect the other end of the same cable to CBP terminal RTN B1 CB3 (see
Figure 5-14 [p. 5-30]).
31 Connect both ends of cable MA of the power harness as follows:
a. Identify lug MA in the power harness (see Figure 5-10 [p. 5-25]) and connect it to shelf
terminal MAIN A (see Figure 5-16 [p. 5-32]).
b. Connect the other end of the same cable to CBP terminal BATT A1 CB3 (see
Figure 5-14 [p. 5-30]).
32 Connect both ends of cable MB of the power harness as follows:
a. Identify lug MB in the power harness (see Figure 5-10 [p. 5-25]) and connect it to shelf
terminal MAIN B (see Figure 5-16 [p. 5-32]).
b. Connect the other end of the same cable to CBP terminal BATT B1 CB3 (see
Figure 5-14 [p. 5-30]).