CHAPTER 2
Core Configuration
Installing Power, Ground, and Alarm Cables
2-37
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
Table 2-1: Power, Ground, and Alarm Cable Connections
(Core Configuration)
Part Number Use Description Term Type Wire Gauge
HA15B-0001-C413 –48 V DC and
ground
5-wire rack/shelf power harness,
one set per shelf
10 AWG crimp
lugs
10 AWG
HA660-1106-T003 Rack alarms 6-connector daisy-chained alarm
harness, one connector per shelf
(CNA through CNF), one harness
per rack
D-sub 25-pin,
terminates with
wire-wrap at CBP
24 AWG
HA660-1102-T015 Shelf alarms Alarm cable from rack alarm cable
connector to shelf backplane alarm
connector, one per shelf
D-sub 25-pin,
CN1 at rack
alarm end, CN2
at shelf alarm end
24 AWG
PC15L-0001-C045 Frame ground Frame ground stranded wire cable
from rack to CBP, one per rack
Terminal lugs,
both ends,
installed
6 AWG, stranded