64 ADL300 • Functions description and parameters list
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.27 680 Full scale speed rpm INT16 CALCI 50 32000 RWZ FVS
Setting of the reference value for all speed percentage data (References, Speed adaptives ...) corresponding to 100 % of
the actual speed. This parameter can only be changed with the inverter blocked (Enable drive = Disabled). The recom-
mended setting for the value of this parameter is the motor rated speed. If altered, the self-tuning procedure should be
repeated.
Full scale speed does not dene the maximum possible speed. In any case, the maximum speed percentage value is ±
200 % of the Full scale speed value.