ADL300 • Functions description and parameters list 61
14 - MOTOR DATA
From this menu you can enter the motor plate data and “basic” values for the voltage/frequency characteristics. It is important to
enter the correct data in order to optimize drive operation and that of the application as a whole. These data are required in order to
obtain:
a) Computation of the normalization factors necessary for regulation
b) Computation of the estimated values for the motor parameters necessary for regulation
Rated voltage, Rated speed, Rated frequency, Rated current, Cos phi, Basic voltage and Basic frequency must be entered (the Cos
phi default value can be used if this value it not present on the plate). After entering these parameters, send a Take parameters
command to calculate (a) and (b) above. The motor cannot be enabled until the Take parameters command has been set. If some
results are inconsistent, or if the motor is much smaller than the inverter, an error message is displayed indicating a numerical ca-
pacity overow and the previous set of parameters is restored in the “Mot plate data” sub-menu.
Example of kW and HP motor data plates
P.2006 P.2000 P.2002
P.2012
P.2006 P.2000 P
.2002
P.2012
3kW
Motor: 3 phase
1420 rpm
Motor&Co.
Type: ABCDE
400 V
IP54
Made in ..............
6.7A
IEC 34-1/VDE 0530
IsoKlF
Nr
.
12345-91
S1
50 Hz
Power factor
0.8
I nom
Rated voltage
Rated power
Rated speed (n )
N
2Hp
Motor: 3 phase
1750 rpm
Motor&Co.
Type: ABCDE
575 V
IP54
Made in ..............
2A
IEC 34-1/VDE 0530
IsoKlF
Nr
.
12345-91
S1
60 Hz
Power factor
0.83
I nom
Rated voltage
Rated power
Rated speed (n )
N
Efficiency
86.5
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.1 2000 Rated voltage V FLOAT SIZE 50.0 690.0 RWZS FVS
Set the motor rated voltage as indicated on the data plate. This is the voltage the drive must supply at the motor rated
frequency.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.2 2002 Rated current A FLOAT SIZE 1.0 1500.0 RWZS FVS
The motor rated current at its rated power (kW / Hp) and voltage (indicated on the motor data plate).
If using a single drive to control several motors connected in parallel (only possible in the SSC mode), enter a value that
corresponds to the sum of the rated currents of all the motors; in this case do not perform any “self-tuning operations”.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.3 2004 Rated speed rpm FLOAT SIZE 10.0 32000.0 RWZS FVS
Rated speed of the motor with full load in rpm (rpm = m-1). In some motors the synchronous speed (e.g. 1500 rpm for a
4-pole motor) and slippage, i.e. the loss of revolutions between the motor idling condition and the rated load condition (e.g.
80 rpm), is indicated. Enter the following: synchronous speed - slippage.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.4 2006 Rated frequency Hz FLOAT SIZE 10.0 1000.0 RWZS FVS
Rated frequency of the motor expressed in Hz, at which the ux weakening range starts.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.5 2008 Pole pairs UINT16 SIZE 1 20 RWZS FVS
Motor pole pairs. The number of motor pole pairs is calculated using the motor plate data and applying the following formula:
p =
60 [s] x f [Hz]
nN [rpm]
Where: p = motor pole pairs; f = motor rated frequency (PAR 2006)
nN = motor rated speed (PAR 2004)

Table of Contents

Other manuals for gefran SIEIDrive ADL300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran SIEIDrive ADL300 and is the answer not in the manual?

gefran SIEIDrive ADL300 Specifications

General IconGeneral
Brandgefran
ModelSIEIDrive ADL300
CategoryInverter
LanguageEnglish

Related product manuals