ADL300 • Functions description and parameters list 73
17 - REGULATOR PARAM
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.1 2250 Current reg P gain V/A FLOAT CALCF 0.0 0.0 ERWS F_S
Setting of the proportional coe󰀩cient of the current regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.2 2252 Current reg I time ms FLOAT CALCF 0.01 10000.0 ERWS F_S
Setting of the integral coe󰀩cient of the current regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.3 2260 Flux reg P gain A/Wb FLOAT CALCF 0.0 0.0 ERWS F__
Setting of the proportional coe󰀩cient of the ux regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.4 2262 Flux reg I time ms FLOAT CALCF 0.01 10000.0 ERWS F__
Setting of the integral coe󰀩cient of the ux regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.5 2264 Flux reg P gain OL A/Wb FLOAT CALCF 0.0 0.0 ERWS __S
Setting of the ux regulator proportional gain when the drive is used in open loop sensorless vector control mode. This
parameter is set automatically by the self-tuning procedure.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.6 2266 Flux reg I time OL ms FLOAT CALCF 0.01 10000.0 ERWS __S
Setting of the ux regulator integral time when the drive is used in open loop sensorless vector control mode. This param-
eter is set automatically by the self-tuning procedure.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.7 2270 Voltage reg P gain Wb/V FLOAT CALCF 0.0 0.0 ERWS F_S
Setting of the proportional coe󰀩cient of the voltage regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.8 2272 Voltage reg I time s FLOAT CALCF 0.1 100.0 ERWS F_S
Setting of the integral coe󰀩cient of the voltage regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.9 2280 Dead time limit V FLOAT SIZE 0.0 50.0 ERWS FVS
Setting of the dead time voltage compensation value.
The dead time compensation function (Dead time compensation), compensates the distortion of output voltage caused
by the voltage drop on the IGBT devices and their switching characteristics.
Distortion of output voltage could cause irregular motor rotation.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.10 2282 Dead time slope V/A FLOAT SIZE 0.0 200.0 ERWS FVS
Setting of the dead time compensation slope value.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.11 2290 Voltage base V FLOAT CALCF 50.0 690.0 ERWS F_S
Setting of the basic voltage of the motor. This parameter is calculated automatically by the self-tuning procedure.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.12 2292 Voltage margin perc FLOAT 5.0 0.0 10.0 ERWS F_S