46 ADV100 • Quick installation guide - Specifications and connection
Braking resistors may be subject to unexpected overloads due to faults.
Resistors MUST be protected using thermal cutouts. These devices must not interrupt the circuit in which the resistor is
inserted but their auxiliary contact must cut off the power supply to the power section of the drive. If the resistor requires a
protection contact, this must be used together with that of the thermal cutout.
A la suite de pannes, les résistances de freinage peuvent être sujettes à des surcharges imprévues. La protection des
résistances au moyen de dispositifs de protection thermique est absolument capitale. Ces dispositifs ne doivent pas
interrompre le circuit qui abrite la résistance, mais leur contact auxiliaire doit couper l’alimentation du côté puissance du
drive. Si la résistance prévoit un contact de protection, ce dernier doit être utilisé conjointement à celui du dispositif de
protection thermique.
Note! For the combination of recommended braking resistors refer to chapter 5.4.
Warning!

Table of Contents

Other manuals for gefran SIEIDrive ADV100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran SIEIDrive ADV100 and is the answer not in the manual?

gefran SIEIDrive ADV100 Specifications

General IconGeneral
Brandgefran
ModelSIEIDrive ADV100
CategoryController
LanguageEnglish

Related product manuals