8.8.2 Saving of parameters on the keypad
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
05 REFERENCES
x5
04 DRIVE CONFIG
16/20 PAR: 590
Save par to keypad
Press E to execute
E
Drive - - > K2006- 1


Menu 04 DRIVE CONFIG, parameter 04.16 Save par to keypad, PAR: 590. This is used to transfer the parameters
from the drive to the selected keypad memory. To start the operation, press the E key.
During transfer, a bar is displayed which indicates progress of the operation.
Instead of the letter X, the number of the currently selected keypad memory is displayed.
At the end of transfer, if this has been completed successfully, the “Done” caption is displayed for a few seconds with
subsequent return to the initial page.
If an error occurs during transfer, the following message is displayed:
Message 01
Save par failed
Code:
XX
Press ESC to exit
The code XX indicates the type of error, see
paragraph 10.3. To exit the error message, press the ESC key.
8.8.3 Load parameters from keypad
Menu 04 DRIVE CONFIG, parameter 04.17 Load par from keypad, PAR: 592. This is used to transfer the parameters
from the selected memory of the keypad to the drive.
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
05 REFERENCES
x4
04 DRIVE CONFIG
17/20 PAR: 592
Load par from keypad
Press E to exe
c
ute
E
Drive < - - K2006- 1

To start the operation, press the E key. During transfer, a bar is displayed which indicates progress of the operation.
Instead of the letter X, the number of the currently selected keypad memory is displayed.
At the end of transfer, if this has been completed successfully, the “Done” caption is displayed for a few seconds with
subsequent return to the initial page.
If an error occurs during transfer, the following message is displayed:
Message 01
Load par failed
Code:
XX
Press ESC to exit
The code XX indicates the type of error, see
paragraph 10.3. To exit the error message, press the ESC key.
8.8.4 Transfer of parameters between drives
Transfer the parameters of the source drive to the keypad memory as indicated in paragraph 8.8.2, then connect the
keypad to the drive where the new setting is to be saved and follow the procedure described in paragraph 8.8.3.
To prevent possible damage to equipment, it is advisable to disconnect and connect the keypad with the drive off.
Caution

Table of Contents

Other manuals for gefran SIEIDrive ADV100

Related product manuals