Limits
Speedlimitsandcurrentlimitsdrivesetting:
T current lim Currentlimitsetting(seechapter6.5.2formoredetails).
Flux current max MaximumeldcurrentvalueaspercentageofMotor d curr.
Flux current min MinimumeldcurrentvalueaspercentageofMotor d curr.(Seechapter6.5.3for
moredetails).
Speed min amount Minimumspeedreferencelimit.(seechapter6.5.1formoredetails).
Speed max amount Maximumspeedreferencelimit.(seechapter6.5.1formoredetails).
Speed feedback
Speedfeedbacksetting(seechapter6.11.5formoredetails):
Speed fbk sel Speedfeedbackselection
Tacho scale Tachgeneratorfeedbackscaling(Speed fbk selmustbesettoTacho).
Speed offset Speedfeedbackoffset
Encoder 2 pulses NumberofpulsesperrevolutionofthedigitalencodertotheXE2connector.
Enable fbk contr Speedfeedbacklosscontrol.TheMotor max speed,Max out voltage,Flux weak
speed parametersmustbesetcorrectlyaccordingtothemotorused.
Refresh enc 2 Enablethemonitoringoftheencoder2(XE2connector)connectionstatus(A,B,Anot,
Bnotchannels).Enable fbk contrmustbeenabled.
Alarms
OvervoltageandOvercurrentthresholdsetting(seechapter6.11.7formoredetails):
Warning Cfg CongurationoftheTPD32-EVdrivebehaviourduringmulti“Warning”situationand
startwithwarningactiveattivi(seechapter5.3.4).
Undervolt thr ACinputalarmthresholdvalue
Overcurrent thr Overcurrrentalarmthresholdvalue.
Overload control
Currentoverloadsetting(seechapter6.14.6formoredetails):
Enable overload Currentoverloadcontrolenabling.
Overload mode Overloadcurrentmodeselection(Currlimited,Currnotlimited,I2tMotor,I2tDrive,
I2tmotor&I2tdrive).
Overload current Driveoutputcurrentpermissibleduringtheoverloadtime.
Base current Driveoutputcurrentpermissibleduringthepausetime.
Overload time Maximumtimeinwhichthe Overload current ispermissible.
Pause time Minimumtimebetweenoverloadcycles.