EasyManua.ls Logo

gefran TPD32-EV-500 series - Reactors; Filters; AC Input Choke

gefran TPD32-EV-500 series
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
—————— TPD32-EV ——————
94
4.10 REACTORS / FILTERS
ToimprovesafetyduringuseoftheTPD32-EVseriesofconverters(mainsnoise,disturbancebetweendrives)
andguaranteecompliancewiththeconditionsasrequiredunderEN60146-1-1,IEC146-1-2andEN61136-1,
athree-phasemainschokeshouldbeinstalledupstreamoftheequipment.Inthemajorityofcases,givenarela-
tiveshort-circuitvoltageofatleast100kAandasimultaneityfactorof1(EN50178,A6.3.6),theinclusionof
aswitchingchoke(ortransformer)withrelativevoltagedropofUK=4%guaranteescommutationnotchesat
thecommoncouplingpoint(CCP)withanamplitudeoflessthan20%.
4.10.1 AC input choke
AccordingtoEN61800-3standard(TableB.1),themax.allowabledepthofthecommutationnotchesinthe
PCislimitedto20%-40%dependingontheinstallationenvironment.Thismaybeobtainedinstallingsuitable
decouplingreactorsortransformers.
Ontheotherhand,foraproperoperation,thedriveshallbeconnectedtoanelectricalsupplylinehavingare-
actancewitharelativevoltagedropofbetween2%(min)and10%(max).Thedecouplingreactancerequiresa
speciccalculationbasedontherelativeshort-circuitpowerRSCattheconnectionpointandtheactualtypeof
connection(singleormultipledrives,separatingtransformers,etc.).But,asanindication,thefollowingtables
listthedecouplingreactancevaluesLd(mainsspool)havingarelativevoltagedropof2%or4%.Thevalue
referstoadriveratedoutputcurrent,butcanbecalculatedforthemotorDCratedcurrent.Thelinecurrentvalue
isgivenbyILN=IdNx0.82.(Onshowncalculationsasafetymarginof+5%hasbeenadded).Itshouldalso
benotedthatdriveshavingsuchahighrelativevoltageusuallybelongtothe"secondenvironment".
Thecalculationformulais:
Ld=(Ukd*
UlN)/(IdN*√2*2π*fN)orLd=(Ukd*UlN)/(IlN*√3*2π*fN)[H]
Table 4.10.1: Mains chokes for 400 Vac input supply
TPD32 EV
Standard sizes
Converter rated current
Rated inductance with
Ukd = 2%
Rated inductance with
Ukd = 4%
Rated current inductance
[A] [µH] [µH] [A]
Mains voltage 400 V, 3 ph, 50 Hz
TPD32-EV-500/...-20-…-A 20 900.3
See "Table 4.10.5 Internal
code for mains chokes" on
page 98
17
TPD32-EV-500/...-40-…-A 40 450.2 34
TPD32-EV-500/...-70-…-A 70 257.2 60
TPD32-EV-500/...-110-…-A 110 163.7 95
TPD32-EV-500/...-140-…-A 140 128.6 121
TPD32-EV-500/...-185-…-A 185 97.3 159
TPD32-500/…-280-…-B 280 64.3 241
TPD32-500/…-350-…-B 350 51.4 301
TPD32-500/…-420-…-B 420 42.9 362
TPD32-500/…-500-…-B 500 36.0 431
TPD32-500/…-650-…-B 650 27.7 560
TPD32-EV-500/...-770-…-C 770 23.4 663
TPD32-EV-500/...-1000-…-C 1000 18.0 861
TPD32-EV-500/...-1050-…-C 1050 17.1 904
TPD32-EV-500/...-1400-...-D 1400 12.9 25.7 1205
TPD32-EV-500/...-1600-...-D 1600 11.3 22.5 1378
TPD32-EV-500/...-2000-...-D 2000 9.0 18.0 1722
TPD32-EV-500/...-2400-...-D 2400 7.5 15.0 2066
TPD32-EV-500/...-1200-…-E 1200 15.0 30.0 1033
TPD32-EV-500/...-1500-…-E 1500 12.0 24.0 1292
TPD32-EV-500/...-1700-…-E 1700 10.6 21.2 1464
TPD32-EV-500/...-1800-…-E 1800 10.0 20.0 1550
TPD32-EV-500/...-2000-…-E 2000 9.0 18.0 1722
TPD32-EV-500/...-2400-…-E 2400 7.5 15.0 2066

Table of Contents