—————— TPD32-EV ——————
182
6.11 CONFIGURATION
6.11.1 Operating mode selection
CONFIGURATION
[252] Maincommands
[253] Controlmode
Parameter description No.
Value
Standard
Conguration
min max
Factory
American
Factory
Standard
Main commands
Terminals(0)
Digital(1)
252 0 1 Term.(0) Term.(0)
-
Control mode
Local(0)
Bus(1)
253 0 1 Local(0) Local(0)
-
Main commands ThesecommandsspecifyfromwheretheEnable drive,StartandFast stopcommands
aretobeactuated.
Terminals Theabovecommandsare actuatedexclusivelyviathe
terminalstrip.
Digital Commandsmustbeselectedbothviatheterminalstripand
viathedigitalchannel(keypadorRS485orbus,depending
onthe Control mode).If,forexample,astopofthedriveis
initiatedbyremovingtheStart commandonterminal13,both
thevoltageonterminal13andthecommandviathedigital
channelarenecessarytorestartthedrive.Thisalsoappliestoa
removaloftheFast stop command.IftheStopisinitiatedvia
thedigitalchannel,thedigitalcommandissufcienttorestart
thedrive.
Thecontrolmethodthroughterminalcommands(Terminals)isselectableonlywhen
terminals12(Enable)and13(Start)arenotsupplied.
CarryingoutthepassageofthecommandsfromDigitaltoTerminalswiththoseterminals
supplied,itwillappearthemessage“Change input”,signallingthewrongaction.
Control mode Deneswhetherthedigitalchannelisthekeypad/RS485orabussystem(Option).
Local ThedigitalchannelisthekeypadortheRS485serialinterface
Bus Thedigitalchannelisabussystem(Option)
Thefollowingtablesshowtheoperatingmodespossible.