—————— TPD32-EV ——————
198
Alarm N.
Factory
Standard
Activity Latch Open
OK relay
Hold off
time [ms]
Restart
time [ms]
Failure Supply
Disabledrive ON ON - - -
Undervoltage
Disabledrive ON ON 0 1000 Dig.Outp.7*
Overvoltage
Ignore ON ON 0 0 Dig.Outp.6*
Overspeed
Ignore ON ON 0 0
Heatsink
Disabledrive ON** ON - - *
Overtemp motor
Disabledrive ON** ON - - *
External fault
Disabledrive ON ON 0 0 *
Brake fault
Disabledrive ON** ON - - -
Motor I2t ovrld
Disabledrive ON ON - - -
Drive I2t ovrld
Disabledrive ON** ON - - -
Overcurrent
Ignore ON ON 0 0 Dig.Outp.8*
Field loss
Disabledrive ON ON 0 0 *
Delta frequency
Ignore ON ON 0 0
SSC error
Disabledrive ON** ON - -
Speed fbk loss
Disabledrive ON** ON 8 - *
Opt 2 failure
Disabledrive ON ON - - *
Bus loss
Disabledrive ON ON 0 0 *
SCR test
Disabledrive ON ON - - -
Hw Opt 1 failure
Disabledrive ON** ON - - *
Enable seq err
Disabledrive ON ON - -
GD6160g
*Thisfunctioncanbeassignedtooneoftheprogrammabledigitaloutputs.**Settingcannotbechanged.
Iftheserialinterfaceorabussystemisused,thealarmscanbeevaluatedviatheMalfunction Codeparameter.
TheparametersrequiredtocongurethealarmareshowninTableinSection10ofthemanual.
Activity Warning Thealarmdoesnotcausereactionofthedrive.Awarning
messagecanbeoutputviaadigitaloutput.Whenthedriveis
disabled,itwillnotrestartuntilthefailurehasbeencanceled.
Disabledrive Thealarmcausestheimmediatedisablingoftheconverter.The
motorrunstoanuncontrolledstop.
Quickstop Whenthealarmoccurs,thedrivestopsaccordingtotherampsetin
theRAMP/QUICKSTOPmenu.Theconverteristhendisabled.
Normalstop Whenthealarmoccurs,thedrivestopsaccordingtotheramp
set.Theconverteristhendisabled.
Currlimstop Whenthealarmoccurs,theconverterbrakeswiththemaximum
possiblecurrent.Theconverteristhendisabledwhenstopped.
Ignore Noreactionispresent.Awarningmessagecanbeoutputviaa
digitaloutput.
Notallalarmscaninitiateacontrolledstopofthedrive.Thepossibilityofsettingthe
particular“Activity”forindividualalarmsisdescribedinthetablebelow.
Alarm Ignore Warning Disable drive Quick stop Normal stop Curr lim stop
Failure Supply
- - X - - -
Undervoltage
- - X - - -
Overvoltage
X X X - - -
Overspeed
X X X X X X
Heatsink
- X X X X X
Overtemp motor
X X X X X X
External fault
- X X X X X
Brake fault
X X X X X X
Motor I2t ovrld
X X X - - -
Drive I2t ovrld
- - X - - -
Overcurrent
X X X - - -
Field loss
X X X - - -
Delta frequency
X X X - - -
SSC error
- - X - - -
Speed fbk loss
- X X - - -
Opt 2 failure
- - X X X X