EasyManua.ls Logo

gefran TPD32-EV-500 series - Page 212

gefran TPD32-EV-500 series
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
—————— TPD32-EV ——————
212
takesthevaluepresetviakeypadorRS485orBUS,beforetoassignananaloginput.
Exceptionarethe“PAD”parameters,wherethelastvalueontheanaloginputisstored
whenAninXXtarget=notassignedisexecuted.
Input XX type Selectionofinputtype(voltageorcurrentinput)
JumpersontheregulatorcardoftheTPD32-EVshouldbettedorremovedaccording
totheinputsignalused.Theinputsofthedevicearefactorysetforvoltagesignls.
Analog Input Input Signal
-10 V ... + 10 V
0 - 10 V
0 - 20 mA
4 - 20 mA
Analoginput1 S9=OFF S9=ON
Analoginput2 S10=OFF S10=ON
Analoginput3 S11=OFF S11=ON
GD6185g
ON Jumpertted
OFF Jumpernottted
10V...+10V Avoltageofmax±10Visconnectedtotheanaloginputconcerned.
Ifthesignalisusedasareferencevalue,apolarityreversalcan
beusedtoreversetherotationdirectionofthedrive(onlywith
TPD32-EV...4B converters).TheTPD32-EV...2Bconverters
acceptasspeedreferenceonlypositivereferences.Negativerefer-
encesarenotacceptedandthedrivedoesnotstart.
0-10V,0-20mA Avoltageofmax.10Voracurrentsignalof0...20mAis
connectedtotheanaloginputconcerned.Thesignalmustbe
positive.IfthesignalisusedasareferencevalueforTPD32-
EV...4Bconverters,therotationdirectioncanbereversedvia
theInput XX sign +andInput XX sign -parameters.
4-20mA Acurrentsignalof4...20mAisconnectedtotheanaloginput
concerned.Thesignalmustbepositive.Ifthesignalisused
asareferencevalueforTPD32-EV...4Bconverters,thedrive
rotationdirectioncanbereversedviatheInput XX sign +
andInput XX sign -parameters.
Input XX sign Selectionofrotationdirectionwhenoperatedviatheserialinterfaceorbusforthetet-
raquadrantTPD32-EV...4Bconverters.
Input XX sign + Selectionof“Clockwise”rotationwhenoperatedviatheterminalstripfortheTPD32-
EV...4Bconverters,whenthereferencevalueisonlygivenwithonepolarity.
High Clockwiseselected
Low Clockwisenotselected
Input XX sign - Selectionof“Counter-clockwise”rotationwhenoperatedviatheterminalstripforthe
TPD32-EV...4Bconverters,whenthereferencevalueisonlygivenwithonepolarity.
High Counterclockwiseselected
Low Counterclockwisenotselected
IfbothInput XX sign+andInput XX sign-are0or1thereferencevalueiszero.
Scale input XX Scalingofthecorrespondinganaloginput
1)
Withascalingfactorof1andaTune value inp XX=1,10Vor20mAonthe
inputcorrespondtotheSpeed base value.
2)
Withascalingfactorof1andaTune value inp XX=1,10Vor20mAonthe
inputcorrespondtomaxpossiblecurrent.
3)
Withascalingfactorof1,10Vor20mAintheinputcorrespondtothePadvalueof2047.

Table of Contents

Related product manuals