—————— TPD32-EV ——————
218
=100%andisre-enabledwhenDrive I2t accum=0.
8)
 I2tmotoroverloadalarmsignal.
9)
 I2tdriveoverloadalarmsignal.
10)
 currentthresholdexceededsignal.
11)
 overspeedalarmsignal.
12)
 frequencyalarmsignal.
13)
 Thefollowingdriveconditionissignalled,viaadigitaloutput:
-regulatorpowersupplypresent
-noalarmspresent
14)
 Thefollowingdriveconditionissignalled,viaadigitaloutput:
-powersupplypresent
-noalarmspresent
-Enablesignalpresent
-three-phasenetworksynchronisationachieved
-excitationcurrentpresent(onlynecessaryifFieldLossalarmActivityisother
thanIGNORE)
15)
Asignalissentviaadigitaloutputtoindicatewhetherthedriveisinadatatransfer
viaeldbuscondition(Controlmode=BUS).
16)
 Indicatestheabsenceofcommunicationbytheslavewiththree-phaseexternal
excitercontrol.
17)
 ActivewhentheconverterisringtheSCRsofthearmaturebridge.
18)
 Activewhentheconverteroutputcurrentiscontinuous.Itsvaluehastobecon-
sideredonlywhenthearmaturepowersectionoftheconverterispowered.
Inversion out XX Reversethedigitaloutputssignal.
Relay 2 Selectionoftheparameters,thatareassignedtotherelaycontactonterminals75and76has
totrip.
note! Asforanalarmsignalthefollowingarevalid:
Output=Lowandopenrelaycontact: Alarm
Output=Highandclosedrelaycontact: Noalarm
Seethechaptersconcerningtheoutputbehaviorwithothermessages.