242
Parameter description No.
Value
Standard
Conguration
min max
Factory
American
Factory
Standard
Enab multi rmp
Enabled(1)/Disabled(0)
243 0 1 Disabled Disabled
-
Ramp selector
202 0 3 0 0
-
Acc delta speed0 [FF]
659 0 2
32-1
100 100
-
Acc delta time 0 [s]
660 0 65535 1 1
-
S acc t const 0 [ms]
665
0 15000
300 300
Dec delta speed0 [FF]
661 0 2
32-1
100 100
-
Dec delta time 0 [s]
662 0 65535 1 1
-
S dec t const 0 [ms]
666
0 15000
300 300
Acc delta speed1 [FF]
23 0 2
32-1
100 100
-
Acc delta time 1 [s]
24 0 65535 1 1
-
S acc t const 1 [ms]
667
0 15000
300 300
Dec delta speed1 [FF]
31 0 2
32-1
100 100
-
Dec delta time 1 [s]
32 0 65535 1 1
-
S dec t const 1 [ms]
668
0 15000
300 300
Acc delta speed2 [FF]
25 0 2
32-1
100 100
-
Acc delta time 2 [s]
26 0 65535 1 1
-
S acc t const 2 [ms]
669
0 15000
300 300
Dec delta speed2 [FF]
33 0 2
32-1
100 100
-
Dec delta time 2 [s]
34 0 65535 1 1
-
S dec t const 2 [ms]
670
0 15000
300 300
Acc delta speed3 [FF]
27 0 2
32-1
100 100
-
Acc delta time 3 [s]
28 0 65535 1 1
-
S acc t const 3 [ms]
671
0 15000
300 300
Dec delta speed3 [FF]
35 0 2
32-1
100 100
-
Dec delta time 3 [s]
36 0 65535 1 1
-
S dec t const 3 [ms]
672
0 15000
300 300
Ramp sel 0
Value2
0
notselected(0)
Value2
0
selected(1)
403 0 1 0 0
*
Ramp sel 1
Value2
1
notselected(0)
Value2
1
selected(1)
404 0 1 0 0
*
*Thisfunctioncanbeassignedtooneoftheprogrammabledigitalinputs.
Enab multi rmp Enabled TheMultirampfunctionisenabled
Disabled TheMultirampfunctionisdisabled
Ramp selector ItisthewordrepresentatonofthetwoparametersRamp sel 0(bit0)andRamp sel 1
(bit1).Usedtochangetherampselectionbychangingonlyoneparameterinsteadof
two.ThisallowstoselectdifferentrampsviaseriallineorBusinstantaneously.
Acc delta speed 0 ItdenestogetherwithAcc delta time 0theaccelerationramp0.Denedbytheunits
speciedinthefactorfunction.
Acc delta time 0 ItdenestogetherwithAcc delta speed 0theaccelerationramp0.Denedinseconds.
S acc t const 0 DenestheaccelerationcurveforS-shaperamp0.Denedinms.
Dec delta speed0 ItdenestogetherwithDec delta time 0thedecelerationramp0.Denedbytheunits
speciedinthefactorfunction.
Dec delta time 0 ItdenestogetherwithAcc delta speed 0 theaccelerationramp0.Denedinseconds.
S dec t const 0 Denesthedecelerationcurvefor S-shape ramp 0.Denedinms.
Acc delta speed1 ItdenestogetherwithAcc delta time 1theaccelerationramp1.Denedbytheunits
speciedinthefactorfunction.
Acc delta time 1 ItdenestogetherwithAcc delta speed 1theaccelerationramp1.Denedinseconds.
S acc t const 1 DenestheaccelerationcurveforS-shape ramp 1.Denedinms.