—————— TPD32-EV ——————
270
zerospeed,theconverterisblockedafteratimespansetby Spd
0 trip delay.Therelaycontactbetweentheterminals75/76
opensafteratimespansetbyTrip cont delay.
Faststp&spd0 TheFastStopcommanddeterminesthebehavior.IftheFast
Stopcommandispresent(digitalorviaterminalstrip;f.e.with
0Vontheterminal14)andthedriveisstopped,theconverteris
blockedandthecontactisopen.WhentheFastStopcommand
isdisabled(i.e.with24Vontheterminal14),Theconverteris
enabledandthecontactisclosed.EnteringtheFastStopcom-
mand,whenthezerospeedhasbeenreached,theconverteris
blockedafteratimespansetwithSpd 0 trip delay.
Fst/stp&spd0 TheFastStopandStartcommandsdeterminethebehavior.When
theStoporFastStopcommandsarepresentandthedriveisstopped,
theconverterisblockedandthecontactisopen.WhentheStart
commandisgivenorwhentheFastStopcommandisdisabled,the
converterisblockedandthecontactisclosed.WhentheStartcom-
mandisdisabledorwhenaFastStopcommandisenteredandafter
reachingzerospeed,theconverterisstoppedafteratimespanset
bySpd 0 trip delay.Therelaycontactbetweentheterminals
75/76opensafteratimespansetby Trip cont delay.
Spd 0 trip delay Delaytimeinmsbetweenreachingzerospeedanddisenablingoftheconverter.
Trip cont delay Delaytimeinmsbetweendisenablingandopeningofthecontactbetweentheterminals
75and76.
Jog stop control OFF ThebehaviorselectedbyStop modehasnoinuenceonthe
Jogfunction.
ON Thebehaviorselectedby Stop modeisactivealsoontheJog
function.
Thementioned“contact”canbeeithertheonebetweentheterminals75/76oradigitaloutput(optionTBO).
Inbothcasesduringthedisplayofthemessagethe“Stop control”parametermustbeselected.Thefunction
isfactorysetontherelaycontact.Theopencontact,mentionedinthedescription,correspondsto0Vonthe
digitaloutput,whiletheclosedcontactcorrespondsto+24Vonthedigitaloutput.
note! AtallthedescribedpossiblilitiesforStop mode,thestopsignalontheterminal13mustbe
present.WithMain commands =Digital,itisnecessarytoselectEnable driveparameter
=EnabledviakeypadorBus.