EasyManua.ls Logo

gefran TPD32-EV-500 series - Page 305

gefran TPD32-EV-500 series
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
—————— Instruction manual ——————
305
SetPID out scale sothat,alongwiththemax.analogvalueonAnalog input 2 (Feed-fwd PID =8500)and
withEnable PI PID eEnable PD PID =disable,Speed ref 1 isthesameat2550rpm.
Speed ref 1 willbesetinRPM x4,so:
PID out scale =(2550x4)/8500=1.2
SetPI central v sel =1.
SetPI central v 1 =1
IntheabsenceofacorrectioncarriedoutfromthePIblockoftheregulator,thelinespeedreference(Feed-
forward)mustbemultipliedby1andsentdirectlytothespeedregulatorofthedrive.
Thisapplicationoperatesbyusingproportionalcontrol.Thecorrectionwillbeindicatedinpercentageaccording
tothelinespeed,from0tothemaximum.
ProgramPI top limit andPI bottom limit sothatthemax.correctionofPIblockcorrespondsat20%ofline
speed.
PI top limit andPI bottom limit parametersarethemaximumandminimummultiplierfactorofFeedforward
value.
Atthemax.linespeeditwillcorrespond2550rpmofthemotor(max.feed-forward).
Max.correction=2550x20%=510rpm
2550+510=3060rpm ——>PI top limit =3060/2550=1.2
2550-510=2040rpm ——>PI bottom limit =2040/2550=0.80
whichwilltomultiplythesettingofPI central v 1(=1)by+20%(1.2)and-20%(0.80).
Withthisconguration,havingacorrectionproportionaltothelinespeed,thePIblockisnotabletoapplyten-
sionatspeed=0.Inordertoapplytensioninstopconditions,itisnecessarytouseonthePDblock.
Thegainsofthesinglecomponentshavetobesetwithloadedmachine;itispossibletostarttestswithvalues
belowindicated(defaultvalues):
SetPI P gain PID =10%
SetPI I gain PID =10%
SetPD P gain PID =10%
Incaseusethederivativecomponentforforcingtheregulatoroutputduringvelocitychangesofthesystem,
programmingforexample:
PD D gain PID =5%
PD D lter PID =20ms
Ifnotnecessary,keeptheseparameters=0.
Incaseitisnecessarytocarryoutareferencescascadeforanotherdrive,setPID output onananalogoutput,
forexample:
Analog output 1 / Select output 1= PID output
(withReal FF PID =10000count,Analog output 1 =10V).
note: Ifitisnecessary,asystemwiththeintegralregulationenabled,withfeed-forward=0,and
theneedtoapplytensionofthesystemwithnullerroralsowhenthemachineisstopped,
pleaserefertotheparagraph“GenericPID”.

Table of Contents

Related product manuals