28.9 Component Evaluation
PLC Interface
28.9 Component Evaluation
Preconditions:
● PLC interface connected to GAV.
● Process monitoring active (see Section 11 "Process Monitoring").
● Profile list active (see Section 11 "Process Monitoring").
Inputs:
Input 9 "Profile Selection" must be 0 (0 V) and input 14 "Part Evaluation" must be 1 (24 V).
Outputs:
● Output 8 "Part OK" evaluation is set to 1 (24 V), output 9 "Part NOK" evaluation to 0 (0 V)
and output 5 "Part Finished" to 0 (0 V) at the beginning of the first process (first profile in pro-
file list).
● If a fault occurs during blind rivet processing, output 8 "Part OK" evaluation is set to 0 (0 V)
and output 9 "Part NOK" evaluation to 1 (24 V).
● Output 5 "Part Finished" is set to 1 (24 V) at the end of the last process (last profile in profile
list) and on reaching home position.
The outputs error code 10 to 13 are 0 (0 V). The error code always refers to the evaluation of a
process and is not output while the component is being evaluated.
Relay:
Relay R2 is switched when output 5 "Part Finished" is 1 (24 V).
Relay R3 is switched when output 8 "Part OK" evaluation is 1 (24 V).
Relay R4 is switched when output 9 "Part NOK" evaluation is 1 (24 V).
Example (see screen):
Message "Part Finished", "Part NOK" evaluation, no error code.
Navigation:
AUTO
►MAN
► Menu
► GAV settings
► PLC interface test