6 User Management HIMax System
HI 801 001 E Rev. 4.01 Page 82 of 122
6.2.2 Parameters for User Accounts
To set up new user accounts, the following parameters must be set:
Parameter Description
Username User name or ID to log in to a controller.
The user name must not contain more than 32 characters (recommended:
a maximum of 16 characters) and may only be composed of letters (A ...
Z, a ... z), numbers (0 ... 9) and the special characters underscore «_»
and hyphen «-».
The user name is case sensitive.
Password Password assigned to a user name required for the log-in.
The password must not contain more than 32 characters and may only be
composed of letters (A ... Z, a ... z), numbers (0 ... 9) and the special
characters underscore «_» and hyphen «-»
The password is case sensitive.
Confirm
Password
Repeat the password to confirm the entry.
Access Mode The access modes define the privileges that a user may have.
The following access types are available:
Read: Users may only read information but they cannot modify the
controller.
Read + Operator: Similar to Read, but users may also:
Perform a download to load and start user programs
Configure the processor modules as redundant
Reset cycle time and fault statistics
Set the system time, force, restart and reset modules
Start system operation for processor modules.
Read + Write: Similar to Read + Operator, but users may also:
Create programs
Translate programs
Load programs into the controller
Test programs
Administrator: Similar to Read + Write, but users may also:
Load operating systems.
Modify the main enable switch setting
Change the SRS
Set the system bus modules to "responsible"
Change the IP settings
At least one user must have administrator rights, otherwise the controller
settings are not accepted.
The administrator can cancel the access to a controller to a later time
point by completely deleting the user from the list.
Table 27: Parameters for User Accounts in the PES User Management Scheme
6.2.3 Setting Up User Accounts
A user with administrator rights can access to all user accounts.
Observe the following points when setting up user accounts:
Make sure that at least one user account is assigned with administrator rights. Define a
password for the user account with administrator rights.
After a user account was created in the user management, its password must be used
to access and edit it.
In SILworX, use the Verification function to check the created user account.
The new user accounts are valid once the code has been generated and a download
has been performed to load the project into the controller. All the user accounts
previously saved, e.g., the default settings, are no longer valid.