7 Diagnosis  HIMax System 
HI 801 001 E Rev. 4.01  Page 84 of 122 
7.1.2  Module Status Indicators 
These LEDs are located on the front plate, on the upper part of the module. 
LED  Color  Status  Description 
On  Module in RUN, normal operation 
Blinking1 Module state:  
STOP/OS_DOWNLOAD or 
OPERATE (only with processor modules) 
Run  Green 
Off  Module not in RUN, 
observe the other status LEDs 
On/Blinking1 
Internal module faults detected by self-tests, e.g., 
hardware, software or voltage supply.  
Fault while loading the operating system 
Error  Red 
Off Normal operation 
On 
Module state: 
STOP / VALID CONFIGURATION 
Blinking1 
Module state: 
STOP / INVALID CONFIGURATION or  
STOP / OS_DOWNLOAD 
Stop  Yellow 
Off  Module not in STOP, observe the other status LEDs 
On  Module state: INIT, observe the other status LEDs 
Blinking1 
Module state: LOCKED, observe to the other status 
LEDs 
Init  Yellow 
Off 
Module state: neither INIT nor LOCKED, observe 
the other status LEDs 
Table 30:  Module Status Indicators 
 
7.1.3 Redundancy Indicators 
LED  Color  Status  Description 
On 
Do not remove the module! 
The module is absolutely required for operating the 
HIMax system. Only one module is configured. 
Blinking1 
Do not remove the module! 
The module is absolutely required for operating the 
HIMax system. Multiple redundant modules are config-
ured. 
Ess  Yellow 
Off 
The module is not absolutely required for operation. It 
may be removed, if required. 
On 
The module is operating redundantly with at least one 
additional module. 
Blinking1 
At least one processor module starts system operation 
or less modules than planned are operating redun-
dantly. 
Red  Yellow 
Off  The module is not operating redundantly. 
Table 31:  Redundancy Indicators