HIMax System  9 Lifecycle 
HI 801 001 E Rev. 4.01  Page 99 of 122 
Figure 21 shows the concept of earthing and shielding the 19'' control cabinet. 
 
 Cabinet Frame 
  Cage Nuts Used to Secure the Base 
Plate 
  25 mm² Earthing Straps Used to Con-
nect the Pivoting Frame to the Cabinet 
Frame 
  PE = Protective Earth
 
  EB = Equipotential Bonding  
  Default Connection with HIMA Control 
Cabinets 
  M 2500 Busbar 
  24 VDC Supply 
  Digital Signals, Terminals on Field Ter-
minal Assembly (FTA) 
  Analog Signals, Terminals on Field Ter-
minal Assemby (FTA) 
 Terminals 
  Pivoting or Fixed Frame 
 Base Plate 
Figure 21:  Earthing and Shielding the 19" Control Cabinet 
Mounting the HIMax on a Pivoting Frame 
The components of the cabinet frame   are welded together and function as electrical 
conductive construction element. Short earthing straps with cross-sections of 16 mm² or 
25 mm² are used to conductively connect the pivoting frames, door, mounting rails and, 
optionally, mounting plates to the cabinet frame.