510324 301C User Manual 107
4/07 Honeywell
Specifications
Specifications
Power requirements 301C 17-27 Vac, 50/60 Hz, 8.64 VA
18-36 Vdc, 350mA @ 24 Vdc (8.4 VA)
Operating temperature range -20ºC to 50ºC (-4ºF to 122ºF)
Operating humidity range 0 to 95% RH (non-condensing)
Operating altitude Up to 3000 m (9843 ft)
Network capacity Up to 96 transmitters, 32 per channel
Channels 1, 2 = Modbus and Vulbus
Channel 3 = Modbus only
Channel 4 = slave communication (i.e.
BACNet use)
Communication Up to 609m (2,000 ft) per channel
(length of lines) T-tap maximum = 20m (65 ft) per t-tap,
overall total of 40m (130 feet)
Wireless communication
range:
30m (98.5 ft)
Wireless communication ISM worldwide, range 30 m indoor
User interface Graphic 122 x 32 dot matrix backlit display
User friendly keypad
Visual indicators Power Green LED
Alarm A, B, C Red LED
Fault Amber LED
Tx Amber LED
Rx Green LED
Outputs 4 DPDT relays
Output rating 5A, 30Vdc or 250 Vac (resistive load)
Audible alarm 65dBA at 1 m (3 ft)
Time delays Programmable Before and After delays
Battery 3 volt lithium battery
Enclosure NEMA 4X, ABS-polycarbonate - indoor use
Dimensions (HxWxD) 28 x 20.3 x 7cm (7.99” x 11.02” x 2.76”)
Certifications ANSI/UL 61010-1
CAN/CSA C22.2 No. 61010-1
ETL 116662