Event Menu
Latch Mode
The Latch function is executed on an Event state
It is possible to select the Latch mode by changing the after delay to
latch
The Event stays active until the Silence keypad button is pressed
The Silence keypad button has two functions: Silence the buzzer
and unlatch the event.
When the Silence keypad button is pressed, events in Latch mode
are unlatched and reevaluated. If the Event condition persists, the
Event remains active and returns to Latch mode. If the condition
does not persist, the event is deactivated.
Note: If the Event has a Before delay and the Silence button is pressed
while the Event conditions are still true, the buzzer will be
silenced only for the length of the programmed delay.