510324 301C User Manual 33
4/07 Honeywell
System Programming
Tx Info Menu
Scale Menus (1 and 2)
These menus appear only for certain devices . Scale(1) lets you define
the detection range, minimum and maximum, for the selected device.
Whatever value is specified is the value that will appear at the device
display (if applicable). The Minimum value is generally left at 0.
Scale(2) lets you determine the factor by which to divide the scale
(between 0 and 65535) and the unit of measurement for the selected
scale.
The factor allows you to set very precise scale limits for detection. By
dividing the maximum scale value in the first Scale screen (250 in this
example) by 10, you are able then to display a scale value of 25.0.
The “Units” allow you to select the unit of measurement for the device:
ºF: Sets degree Farenheit as the unit of measurement
ºC Sets degree Centigrade as the unit of measurement
%RH Sets Relative Humidity as the unit of measurement
mV Sets millivolts as the unit of measurement
V Sets volts as the unit of measurement
mA Sets milliamps as the unit of measurement
% Sets the percentage of gas as the point unit of measurement
ppm Sets parts per million of gas as the point unit of
measurement
1. Tx Info 001
-Scale(1)-
Max 00250
Min 00000
1. Tx Info 001
-Scale(2)-
Factor 00010
Units %