EasyManuals Logo

Honeywell 301C User Manual

Honeywell 301C
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
510324 301C User Manual 39
4/07 Honeywell
System Programming
Tx Info Menu
Change Tx Address
Selecting Change Tx Address allows users to move a device from one
TX address to another:
Use the arrows to scroll to Change Tx Address and press Enter to
select
In the next screen, scroll to the address number and press Enter to
select
Use the up or down arrows to increase or decrease the address
value and press Enter to validate the new address.
The Change Tx address option is only available (active) for device
address 1 to 96 and if there is a Modbus device connected.
If the address is valid, the screen will display “Processing”.
If the address is invalid, the screen will display “Invalid Tx” and return to
the Change Tx Address screen (you cannot change the address for
GasPoint devices)
A final screen will display either “Error” or “Success” (re-start procedure
if Error is displayed).
Note: If a device address is changed to an one already associated to
another device, the existing data will be overwritten. Customers
should know their network’s address assignments and be careful
when changing a Tx address.
Remember to delete the original Tx address to avoid duplicate
entries.
1. Tx Info 001
erase current Tx
Change Tx Address
1. Tx Info 001
To address: 001
1. Tx Info 001
Processing...

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell 301C and is the answer not in the manual?

Honeywell 301C Specifications

General IconGeneral
Controller TypeTemperature Controller
Control ModeON/OFF, PID
Input Voltage100-240 VAC
InputThermocouple, RTD
OutputRelay, SSR
Operating Temperature0 to 50°C
Contact Rating5A @ 250 VAC (Relay)