ALPHABETIC REFERENCE EXCEL CARE CONTROL ICONS
74-5577–33 (US) 194
EN2B-0184 GE51 R0518 (Europe)
P4 Integral action time Tn (in seconds). If you set Integral action time to zero in the
internal parameters dialog box, software sets the P4 parameter to 1,000,000. A
number this large effectively disables the integral term.
P5 Minimum output (in percent)
P6 Maximum output (in percent)
P7 Reference variable (W) if entered as a parameter (not connected to a point)
PD Controller
P3 Proportional band Xp
P4 Derivative time Tv (in seconds).
P5 Minimum output (in percent)
P6 Maximum output (in percent)
P7 Reference variable (W) if entered as a parameter (not connected to a point)