INNCOM e7w THERMOSTAT USER GUIDE
41
31-00302-01
The following is a complete example of reading and changing a Group 9 Registry.
Read Registry 9:1 Occupancy, Offset 8 Min_GuestOccupancyTimeout of the HVAC partner to the e7w.
Change from the current value of 10 minutes to 15 minutes.
Press FAN button to store the changes
Use Up/Down button to
set value to 8 , then
press MODE
Value changed to 15
Current Value is 10.
Use Up arrow button to
change value to 15
Press FAN button to
store the new value.
Cloud/Sun symbol blinks
to indicate registry
value has been changed
Value
Value
Value
Press F/C Button 4 times to exit out of rEG menus until Str (Store) appears on display
Use Up/Down button to
select Gr value ,then press
MODE
Use Up/Down button to
select Key value ,then press
MODE
Parameter and value 0 be
displayed. This is Registry 9:1
Offset 0
Press MODE