INNCOM e7w THERMOSTAT USER GUIDE
The following is a complete example of reading and changing a Group 7 Registry.
Read Registry 7:3:1 Light Output, Offset 20 Minlevel of an X45RA Address 30. Lower the current value
of 40 to 20. In order to read the X45RA, which is not the HVAC partner to the e7w, you will need to
change the current e7w Partner Address (PA) of 14 to 30, make the change to the X45RA, then
change the e7w back to the original address of the e7w HVAC partner (14).
Enter Service Mode and select PA parameter.
Press MODE to view value 14
Change value to 30 , press FAN to store change. e7w will
beep and return to display PA
Select rE6 parameter
and press MODE
Change Group value to 7
and press MODE
Change Key value to 3
and press MODE
Change Index value to 1
and press MODE
Parameter and 0 will
appear
Change Parameter value to
20 and press MODE
Current value of 40 is displayed.
Change value to 20 and press FAN to store
Cloud/Sun icon will blink indicating Registry value was
changed.
Press F/C button return to displaying Parameter value
Press F/C button to exit back to Index (Idx) , Key and
Group (Gr.) menus