EasyManua.ls Logo

HT FULLTEST3 - Page 92

HT FULLTEST3
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FULLTEST3
EN - 90
RCD TEST (RCD)
RCD types / characteristics: AC, A or B / General, Selective or Delayed
Measurement modes: ½ I'N, I'N, 2I'N, KI'N (K = 4 B type, K=5 AC, A type)
I' (RAMP), AUTO (sequence: x½ , x1, xK)
Nominal currents: 10, 30, 100, 300, 500, 650 or 1000 Ma
Delayed time range: 0ms ÷ 700ms adjustable
Accuracy of test currents (10 mA): -10% / + 0% (I'N/2), +10% / - 0% (I'N, 2I'N, KI'N)
Accuracy of test currents (30y1000 mA): -5% / + 0% (I'N/2), + 5% / - 0% (I'N, 2I'N, KI'N)
Input voltage range / frequency: 100 Vy 265V / (50/60Hz) ± 0.5Hz
Contact voltage limits: 25 V or 50 V selectable
Test current polarity: 0° (Positive) o 180° (Negative)
Test duration [ms] – TT/TN system
I
'
N
[mA]
×½ ×1 ×2 ×K AUTO RAMP
G, S, D G, S, D G S D G S D G S D G S D
10
30
100
AC 1000 1000 200 250
X 50 150 X

X 320 X X
A 1000 1000 200 250 X 50 150 X

X 320 X X
B 1000 1000 X X X 200 250 X

X 320 X X
300
AC 1000 1000 200 250
X 50 150 X

X 320 X X
A 1000 1000 200 250 X 50 150 X

X 320 X X
B 1000 1000 X X X X X X X X X 320 X X
500
AC 1000 1000 200 250
X 50 150 X

X 320 X X
A 1000 1000 200 250 X X X X X X X 320 X X
B 1000 1000 X X X X X X X X X 320 X X
650
AC 1000 1000 200 250
X 50 150 X

X 320 X X
A 1000 1000 200 250 X X X X X X X 320 X X
B X X X X X X X X X X X X X X
1000
AC 1000 1000 200 250
X X X X X X X 320 X X
A 1000 1000 X X X X X X X X X X X X
B X X X X X X X X X X X X X X
Resolution: 1ms, Accuracy: ± 3%rdg + 2ms)
X = test not possible
Mains voltage UL/N, UL/PE
Range
[V]
Resolution
[V]
Accuracy
100 y 265
1 ± (3%rdg)
Input resistance (UL/N, UL/PE): 450 k:
Ramp test: current range 10% y 110% of I'N in steps of 5% of I'N
AUTO TEST: test steps are as follows: t/I'N/2 (0°), t/I'N/2 (180°), t/I'N (0°),
t/I'N (180°), t/5I'N (0°), t/5I'N (180°)