FULLTEST3
EN - 90
RCD TEST (RCD)
RCD types / characteristics: AC, A or B / General, Selective or Delayed
Measurement modes: ½ I'N, I'N, 2I'N, KI'N (K = 4 B type, K=5 AC, A type)
I' (RAMP), AUTO (sequence: x½ , x1, xK)
Nominal currents: 10, 30, 100, 300, 500, 650 or 1000 Ma
Delayed time range: 0ms ÷ 700ms adjustable
Accuracy of test currents (10 mA): -10% / + 0% (I'N/2), +10% / - 0% (I'N, 2I'N, KI'N)
Accuracy of test currents (30y1000 mA): -5% / + 0% (I'N/2), + 5% / - 0% (I'N, 2I'N, KI'N)
Input voltage range / frequency: 100 Vy 265V / (50/60Hz) ± 0.5Hz
Contact voltage limits: 25 V or 50 V selectable
Test current polarity: 0° (Positive) o 180° (Negative)
Test duration [ms] – TT/TN system
I
N
[mA]
×½ ×1 ×2 ×K AUTO RAMP
G, S, D G, S, D G S D G S D G S D G S D
10
30
100
AC 1000 1000 200 250
X 50 150 X
X 320 X X
A 1000 1000 200 250 X 50 150 X
X 320 X X
B 1000 1000 X X X 200 250 X
X 320 X X
300
AC 1000 1000 200 250
X 50 150 X
X 320 X X
A 1000 1000 200 250 X 50 150 X
X 320 X X
B 1000 1000 X X X X X X X X X 320 X X
500
AC 1000 1000 200 250
X 50 150 X
X 320 X X
A 1000 1000 200 250 X X X X X X X 320 X X
B 1000 1000 X X X X X X X X X 320 X X
650
AC 1000 1000 200 250
X 50 150 X
X 320 X X
A 1000 1000 200 250 X X X X X X X 320 X X
B X X X X X X X X X X X X X X
1000
AC 1000 1000 200 250
X X X X X X X 320 X X
A 1000 1000 X X X X X X X X X X X X
B X X X X X X X X X X X X X X
Resolution: 1ms, Accuracy: ± 3%rdg + 2ms)
X = test not possible
Mains voltage UL/N, UL/PE
Range
[V]
Resolution
[V]
Accuracy
100 y 265
1 ± (3%rdg)
Input resistance (UL/N, UL/PE): 450 k:
Ramp test: current range 10% y 110% of I'N in steps of 5% of I'N
AUTO TEST: test steps are as follows: t/I'N/2 (0°), t/I'N/2 (180°), t/I'N (0°),
t/I'N (180°), t/5I'N (0°), t/5I'N (180°)