LOOP IMPEDANCE / SHORT-CIRCUIT CURRENT (LOOP)
Range [
:
] Resolution [
:
]
Accuracy
Overload
protection
0.000 y 2.000 (*)
0.001
± (3%rdg + 3dgt) CAT III 300 V
0.00 y 9.99
0.01
10.0 y 99.9
0.1
100 y 200
1
(*) With optional accessory IMP57
Input voltage range LOOP L/PE or L/N: 100V y 265V, 50/60Hz
Input voltage range LOOP L/L: 100 y 460V, 50/60 Hz
Nominal mains voltage: 110V, 115V, 120V, 133V, 220V, 230V, 240V
Loading resistance: 10: for 20ms (range 0.00 y 30.0 :) and
180: for 20ms (range 30.0 y 200.0 :)
Short-circuit current (ISC)
Range [A] Resolution [A] Accuracy
0.05 y 0.99
0.01
Depends on U
L/PE and Z accuracy
1.0 y 99.9
0.1
100 y 999
1
1.00k y 46.00k
10
Mains voltage UL/N, UL/PE
Range [V] Resolution [V] Accuracy
100 y 265
1 ±(3%rdg)
Input resistance (UL/N, UL/PE): 450k:
Mains voltage
UL/L
Range [V] Resolution [V] Accuracy
100 y 460
1 ±(3%rdg)
Input resistance (UL/N, UL/PE): 450k: