FULLTEST3
EN - 92
GLOBAL EARTH RESISTANCE WITHOUT TRIPPING RCD (RA)
I
N [mA] Range [
] Resolution [
]
Accuracy (*)
Overload
protection
10
0 y 2000
1
± (3%rdg + 1:)
CAT III 300 V
30
0.0 y 99.9
0.1
100 y 2000
1
100
0.0 y 99.9
0.1
± (3%rdg. + 3dgt)
100 y 1000
1
300
0.0 y 99.9
0.1
100 y 300
1
500
0.0 y 99.9
0.1
100 y 200
1
650
0.0 y 99.9
0.1
100 y 150
1
1000
0.0 y 100.0
0.1
(*) The accuracy in the 10: y2000: range may be affected by instable mains voltage
Test current: I'N /2
Input voltage range: 100 y 265 V, 50/60 Hz
Nominal mains voltage : 110V, 115V, 120V, 133V, 220V, 230V, 240V
Mains voltage UL/PE
Range [V] Resolution [V] Accuracy
100 y 265
1 ± (3%rdg)
Input resistance (UL/PE): 450 k:
Contact voltage UC at I
N
Range [V] Resolution [V] Accuracy
0 y 100 (UC LIM = 50 V)
1 ± (3%rdg. + 3V)
0 y 50 (UC LIM = 25 V)
TRMS RESIDUAL VOLTAGE (URES)
Range [V] Resolution [V] Accuracy
Overload
protection
10 y 460 (AC)
1 ± (3%rdg. + 3V) CAT III 300V
10 y 650 (DC)
Input voltage (UTRIG): 0V y 460 VAC
Nominal mains voltage : 110V, 115V, 120V, 133V, 220V, 230V, 240V
Measurement method: 4-wire connection (INTERNAL measurement, 1s or 5s)
2-wire connection (PLUG measurement, 1 s)
Residual voltage limit value: 60V RMS
Input voltage URES:
Range [V] Resolution [V] Accuracy
10 y 460 (AC)
1 ± (2%rdg + 2V)
10 y 650 (DC)
Input resistance (URES): 100 M:
Input voltage UTRIG:
Range [V] Resolution [V] Accuracy
10 y 265 (AC)
1 ± (2%rdg. + 2V)
Input resistance (UTRIG): 450 k: