EasyManua.ls Logo

Huawei iSitePower-M MAP05A1 - Page 102

Huawei iSitePower-M MAP05A1
221 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. One End Other End Type Recommended
Specications
4 COM and
dry contact
ports
Genset
control signal
Outdoor shielded twisted
pair cable (eight cores)
Conductor cross-
sectional area: 0.2–1
mm
2
Cable outer diameter:
6.3–7.5 mm
5 Ground
point
Site ground
bar
(customer
side)
Outdoor single-core
copper cable
Conductor cross-sectional
area: 4–6 mm
2
(same as
the cross-sectional area of
the AC input power cable)
6 Ground
point
Ground point
on the
module for
capacity
expansion
Outdoor single-core
copper cable (capacity
expansion scenario)
Conductor cross-sectional
area: 6 mm
2
Table 9-10 Cables in parallel-system scenarios
No.
One End Other End Type Recommended
Specications
1 PV input
port
DC switch
(customer
side)
Common outdoor PV
cable in the industry
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
5.5–9 mm
2 Ground
point
Site ground
bar
(customer
side)
Outdoor single-core
copper cable
Main PE cable: 4–6 mm
2
(same as the cross-sectional
area of the AC input power
cable)
3 COM and
dry contact
ports
Genset
control signal
Outdoor shielded twisted
pair cable (eight cores)
Conductor cross-
sectional area: 0.2–1
mm
2
Cable outer diameter:
6.3–7.5 mm
4 AC parallel
box
AC PDC
(customer
side)
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 25 mm
2
Cable outer diameter:
16–26 mm
5 AC parallel
box
AC output
port
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
iSitePower-M (MAP05A1, MAB05B1)
User Manual 9 Preparing Cables
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 93

Table of Contents