No. One End Other End Type Recommended
Specications
4 COM and
dry contact
ports
Genset
control signal
Outdoor shielded twisted
pair cable (eight cores)
● Conductor cross-
sectional area: 0.2–1
mm
2
● Cable outer diameter:
6.3–7.5 mm
5 Ground
point
Site ground
bar
(customer
side)
Outdoor single-core
copper cable
Conductor cross-sectional
area: 4–6 mm
2
(same as
the cross-sectional area of
the AC input power cable)
6 Ground
point
Ground point
on the
module for
capacity
expansion
Outdoor single-core
copper cable (capacity
expansion scenario)
Conductor cross-sectional
area: 6 mm
2
Table 9-10 Cables in parallel-system scenarios
No.
One End Other End Type Recommended
Specications
1 PV input
port
DC switch
(customer
side)
Common outdoor PV
cable in the industry
● Conductor cross-
sectional area: 4–6 mm
2
● Cable outer diameter:
5.5–9 mm
2 Ground
point
Site ground
bar
(customer
side)
Outdoor single-core
copper cable
Main PE cable: 4–6 mm
2
(same as the cross-sectional
area of the AC input power
cable)
3 COM and
dry contact
ports
Genset
control signal
Outdoor shielded twisted
pair cable (eight cores)
● Conductor cross-
sectional area: 0.2–1
mm
2
● Cable outer diameter:
6.3–7.5 mm
4 AC parallel
box
AC PDC
(customer
side)
Outdoor three-core copper
cable (L/N/PE)
● Conductor cross-
sectional area: 25 mm
2
● Cable outer diameter:
16–26 mm
5 AC parallel
box
AC output
port
Outdoor three-core copper
cable (L/N/PE)
● Conductor cross-
sectional area: 4–6 mm
2
● Cable outer diameter:
13.7–16.9 mm
iSitePower-M (MAP05A1, MAB05B1)
User Manual 9 Preparing Cables
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 93