Type Tools and Instruments
Dust mask Protective shoes
-
7.1.3 Determining the Installation Position
Installation Angle Requirement
The battery can be oor-mounted and wall-mounted. The installation angle
requirement is as follows:
Do not install the battery at forward tilted, back tilted, side tilted, horizontal,
or upside down positions.
Installation Position Requirements
Install the battery on a solid brick-concrete structure or concrete wall or
oor.
If other types of walls and oors are used, they must be made of re-
retardant materials and meet the load-bearing requirements of the
equipment.
The bearing capacity of the ground must be greater than or equal to 500
kg/m
2
.
Installation Space Requirements
During installation, ensure that there is no other devices (except related
Huawei devices and awnings) or
ammable or explosive materials around the
batteries. Reserve adequate space for heat dissipation and safety isolation.
When the battery is mounted on a wall, do not place any objects under the
battery.
Installation Dimensions
Reserve
sucient clearance around the product for installation and heat
dissipation.
iSitePower-M (MAP05A1, MAB05B1)
User Manual 7 System Installation
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 73