Table 9-2 (Optional) Cables in capacity expansion scenario
No. Cable Type
1 Power cables for
bottom cascading
Common outdoor PV cables in the industry
2 Signal cables for
bottom cascading
Outdoor shielded twisted pair cables
9.2 Cables Prepared by the Customer
9.2.1 PV+ESS
Table 9-3 Cables in single-system scenarios (including capacity expansion)
No. One End Other End Type Recommended
Specications
1 PV input
port
DC switch
(customer
side)
Common outdoor PV
cable in the industry
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
5.5–9 mm
2 AC output
port
PDB
(customer
side)
Outdoor three-core copper
cable (L/N/PE)
Conductor cross-
sectional area: 4–6 mm
2
Cable outer diameter:
13.7–16.9 mm
3 Ground
point
Site ground
bar
(customer
side)
Outdoor single-core
copper cable
Conductor cross-sectional
area: 4–6 mm
2
(same as
the cross-sectional area of
the AC input power cable)
4 Ground
point
Ground point
on the
module for
capacity
expansion
Outdoor single-core
copper cable (capacity
expansion scenario)
Conductor cross-sectional
area: 6 mm
2
iSitePower-M (MAP05A1, MAB05B1)
User Manual 9 Preparing Cables
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 88