10.2.4 Installing an AC Input Power Cable
D ANGER
A surge protective device (SPD) must be congured for the AC input of the
iSitePower-M. You need to
congure and install the device by yourself.
Before installing an AC input power cable, ensure that the AC input switch is
turned
o and a prominent label indicating "Do not operate" is set.
AC switches (with a capacity of 40 A) must be installed for phases L and N of
the iSitePower-M AC input. The AC switches are delivered with the iSitePower-
M. Do not use a Type D circuit breaker because it cannot
eectively protect
products.
No leakage protection device is required for the AC input of the iSitePower-M.
If a leakage protection device is
congured, it is recommended that the leakage
current be greater than or equal to 100 mA x
n
, where
n
is the number of
power modules.
CA UTION
The live (L) wire and neutral (N) wire of an AC power cable must be correctly
connected.
The PE wire of an AC power cable must be grounded.
Do not reversely connect AC input power cables.
NO TE
In single-system scenarios, connect the other end of the cable to an AC PDC. In parallel-
system scenarios, connect the other end of the cable by referring to section "(Optional)
Installing Parallel Cables."
Procedure
Step 1 Connect an AC power cable to the terminal connector.
Figure 10-15 Connecting the cable to the terminal connector
Step 2 Install the AC input power cable and secure the cable using cable clips.
iSitePower-M (MAP05A1, MAB05B1)
User Manual 10 Electrical Connections
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 111