9 Preparing Cables
NO TICE
Do not use aluminum cables to avoid electrochemical corrosion of copper and
aluminum.
Power cables should be able to withstand a temperature of at least 90°C.
NO TE
The minimum cable cross-sectional area must meet local standards.
The factors that aect cable selection include the rated current, cable type, routing
mode, ambient temperature, and maximum expected line loss.
9.1 Cables Delivered with the Product
Table 9-1 Cables delivered with the product
No.
Cable Type
1 Power cables Common outdoor PV cables in the industry
2 Signal cables Outdoor shielded twisted pair cables
3 PE cables (standard
scenario)
Outdoor single-core copper cables
NO TICE
In capacity expansion scenarios, you need to purchase power cables and signal
cables for bottom cascading from Huawei.
iSitePower-M (MAP05A1, MAB05B1)
User Manual 9 Preparing Cables
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 87