Loading...
Figure 10-32 Installing the PV input power cables
----End
10.4.4 Installing an AC Output Power Cable
CA UTION
The live (L) wire and neutral (N) wire of an AC power cable must be correctly
connected.
The PE wire of an AC power cable must be grounded.
Do not reversely connect AC output power cables.
NO TICE
A leakage protection device must be congured for the AC output of the
iSitePower-M. The leakage current must be 30 mA. You need to congure and
install the device by yourself.
NO TE
In single-system scenarios, connect the other end of the cable to the AC load. In parallel-
system scenarios, connect the other end of the cable to the parallel box.
Procedure
Step 1 Connect an AC power cable to the terminal connector.
Figure 10-33 Connecting the cable to the terminal connector