A Technical Specications
A.1 ESS
Table A-1 Environmental specications
Item Specications
Operating temperature 0–45°C (When the ambient temperature is low,
the battery module charging must be derated.
When the ambient temperature is 0°C to 5°C and
5°C to 10°C, battery modules can be charged at
0.05C and 0.1C, respectively.)
Transportation temperature –40°C to +60°C
Storage temperature –40°C to +60°C
Relative humidity 5%–95% RH
Altitude 0–4000 m. (When the altitude ranges from 2000
m to 4000 m, high temperature derating applies
and the operating temperature decreases by 1°C
for each additional 200 m.)
Noise level ≤ 40 dBA at 1 m at 30°C ambient temperature
IP rating IP66
Operating environment Class C environment
Other requirements ● There should be no conductive dust, corrosive
gas, or explosion hazard.
● Dust, corrosive substances, pests, molds, and
other indicators should be controlled in
accordance with Class 4.1 requirements in ETSI
EN 300 019-1-4 (V2.2.1).
iSitePower-M (MAP05A1, MAB05B1)
User Manual A Technical Specications
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 202