A Technical Specications
A.1 ESS
Table A-1 Environmental specications
Item Specications
Operating temperature 0–45°C (When the ambient temperature is low,
the battery module charging must be derated.
When the ambient temperature is 0°C to 5°C and
5°C to 10°C, battery modules can be charged at
0.05C and 0.1C, respectively.)
Transportation temperature –40°C to +60°C
Storage temperature –40°C to +60°C
Relative humidity 5%–95% RH
Altitude 0–4000 m. (When the altitude ranges from 2000
m to 4000 m, high temperature derating applies
and the operating temperature decreases by 1°C
for each additional 200 m.)
Noise level ≤ 40 dBA at 1 m at 30°C ambient temperature
IP rating IP66
Operating environment Class C environment
Other requirements There should be no conductive dust, corrosive
gas, or explosion hazard.
Dust, corrosive substances, pests, molds, and
other indicators should be controlled in
accordance with Class 4.1 requirements in ETSI
EN 300 019-1-4 (V2.2.1).
iSitePower-M (MAP05A1, MAB05B1)
User Manual A Technical Specications
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 202