No. One End Other End Type Recommended
Specications
6 AC parallel
box
AC input port Outdoor three-core copper
cable (L/N/PE)
● Conductor cross-
sectional area: 4–6 mm
2
● Cable outer diameter:
13.7–16.9 mm
7 AC parallel
box
PDB
(customer
side)
Outdoor three-core copper
cable (L/N/PE)
● Conductor cross-
sectional area: 25 mm
2
● Cable outer diameter:
16–26 mm
8 AC parallel
box
Site ground
bar
(customer
side)
Outdoor single-core
copper cable
● Conductor cross-
sectional area: 25 mm
2
● Cable outer diameter: 8–
11 mm
9.2.5 Mains+Genset+ESS
Table 9-11 Cables in single-system scenarios (including capacity expansion)
No.
One End Other End Type Recommended
Specications
1 AC output
port
PDB
(customer
side)
Outdoor three-core copper
cable (L/N/PE)
● Conductor cross-
sectional area: 4–6 mm
2
● Cable outer diameter:
13.7–16.9 mm
2 AC input
port
AC PDC
(customer
side)
Outdoor three-core copper
cable (L/N/PE)
● Conductor cross-
sectional area: 4–6 mm
2
● Cable outer diameter:
13.7–16.9 mm
3 COM and
dry contact
ports
Genset
control
signal/ATS
detection
signal
Outdoor shielded twisted
pair cable (eight cores)
● Conductor cross-
sectional area: 0.2–1
mm
2
● Cable outer diameter:
6.3–7.5 mm
4 Ground
point
Site ground
bar
(customer
side)
Outdoor single-core
copper cable
Conductor cross-sectional
area: 4–6 mm
2
(same as
the cross-sectional area of
the AC input power cable)
iSitePower-M (MAP05A1, MAB05B1)
User Manual 9 Preparing Cables
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 94