10.7.4 Installing Parallel Communications Cables
NO TICE
Before installing parallel cables, set the same output parameters for the master
and slave products, and then correctly set the address DIP switches for the
master and slave products.
The address DIP switches take
eect only after the devices are restarted. Set
the DIP switches when the devices are powered o (AC and DC inputs are
disconnected, and the devices are shut down by pressing the black start
button).
When installing parallel power communications cables, install termination
resistors at the
rst and last modules. The termination resistors are delivered
with the product.
The length of a single communications cable cannot exceed 3 m.
A parallel power communications cable is installed in the same way as a
battery module communications cable.
Procedure
Step 1 Power on the iSitePower-M systems and set the same output parameters for the
master and slave products.
Step 2 Power
o the iSitePower-M systems and set address DIP switches for the master
and slave products.
Scenario
DIP
Switch
Pin 1 (M/S) Pin 2 (A) Pin 3 (B) Pin 4 (C)
Par
all
el
pr
od
uct
s
Master 1 ON OFF OFF OFF
Slave1 2 OFF ON OFF OFF
Slave2 3 OFF OFF ON OFF
Step 3 Install parallel power communications cables.
iSitePower-M (MAP05A1, MAB05B1)
User Manual 10 Electrical Connections
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 153