Module Alarm Name Alarm
Severity
Causes Suggestion
Genset AC Output
Undervoltage
Minor 1. The genset
is faulty.
1. If the alarm occurs accidentally,
the genset may be abnormal
temporarily. The system
automatically recovers after
detecting that the genset
becomes normal.
2. If the alarm occurs frequently,
check whether the genset output
voltage is within the allowed
range. If not, contact the genset
supplier. If yes, change the output
undervoltage threshold on the
mobile app or management
system.
● FusionSolar app (local
commissioning): Home >
Genset Summary > Device >
Genset1 >
Conguration >
Output Undervoltage
Threshold
● Management system:
Navigate to the device and
choose Genset Summary >
Genset[1] >
Conguration >
Alarm Parameters > Output
Undervoltage Threshold.
3. If the fault persists for a long
time, check whether the output
power cable is properly
connected to the genset AC
output switch.
4. 4. Maintain the genset. If the
fault persists, contact technical
support.