Item Specications
Note [1]: The output voltage and frequency must be the same as those of the
local power grid.
Note [2]: Test conditions: 100% depth of discharge (DOD), 0.2C rate charge &
discharge at 25°C, upon delivery
Table A-3 EMC specications
Item Specications
Electromagn
etic
interference
(EMI)
Conducted
emission (CE)
IEC 62920/CISPR 11/EN 62040-2
AC port: Class B; PV port: Class A; signal
port: Class B; FE port: Class B
Radiated
emission (RE)
IEC 62920/CISPR 11/EN 62040-2
Class B
Harmonic current IEC 61000-3-12
AC power port: The current of each phase is
greater than 16 A.
Voltage
uctuation and
icker
IEC 61000-3-12
AC power port: Pst ≤ 1.0, P1t ≤ 0.65, dc ≤
3%, dmax ≤ 4%. The time when the value of
d(t) exceeds 3% is less than or equal to 200
ms.
Electromagn
etic
susceptibility
(EMS)
Electrostatic
discharge (ESD)
IEC 61000-4-2
Enclosure port: 6 kV (level B) contact
discharge, 8 kV (level B) air discharge
Electrical fast
transient (EFT)
IEC 61000-4-4
AC power port: 2 kV, DC power port: 2 kV,
signal port: 1 kV (criterion B)
Radiated
susceptibility
(RS)
IEC 61000-4-3
Enclosure port: The test frequency range is
80 MHz to 6 GHz, 80% AM (1 kHz)
modulation is used, and the test level is 10
V/m.
Conducted
susceptibility
(CS)
IEC 61000-4-6
0.15–80 MHz: 10 V, 80% AM (1 kHz)
modulation
iSitePower-M (MAP05A1, MAB05B1)
User Manual A Technical Specications
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 204