Parameters Settings
Figure 6-13 Setting basic parameters
Table 6-6 Basic parameters
Parameter
Description
Output Voltage Set the output voltage and output frequency based on the
local power grid standards.
Output Frequency
Rated Power(kW) Set the genset power to prevent genset overload and
system breakdown when ESSs are charged.
Genset Startup
SOC(%)
The value of Genset Startup SOC(%) must be at least
10% greater than the value of End-of-Discharge SOC for
Lithium Batteries(%).
Genset Shutdown
SOC(%)
The genset shuts down when the ESSs charge to the value
of Genset Shutdown SOC(%).